Fire doors

Fire Door Inspection Checklist: Monthly and Annual Checks, Common Failures and Records

Fire door inspection checklist: monthly and annual checks, common failures such as wedged doors and removed closers, safe repairs and inspection records.

Safety Plus technical team · Updated · 8 min read

Why fire doors fail in real buildings

Fire doors rarely fail because of how they were made. They fail because of how buildings are used. A stair door that is in the way of trolleys gets wedged open. A closer that slams gets its arm unhooked. A lost key leads to a padlock. A painter covers the smoke seal. Each change seems small; together they mean the door will not stop smoke on the day it is needed.

Inspection is not paperwork for its own sake. It finds these changes early, while they are cheap to fix, and it produces records that show authorities, buyers and insurers that the building is managed.

In RMG and textile factories, fire doors on stairs and storage areas are a frequent focus of safety inspections. The same discipline applies to hospitals, warehouses and commercial buildings. Combine fire door checks with the rest of your equipment checks using the RMG factory fire safety equipment checklist.

Quick daily or weekly walk-through checks

These take seconds per door and can be done by security, floor supervisors or safety committee members during rounds:

  • Door is closed, or held open only by an alarm-released magnetic holder.
  • Nothing wedges, ties or blocks the door: no chocks, ropes, hooks, stacked cartons or fire extinguishers against the leaf.
  • The path on both sides is clear.
  • The door closes and latches on its own when released from fully open.
  • No padlocks, chains or bolts on escape doors.
  • "Fire door — keep shut" signage is in place.

Anything wrong is reported the same day. A wedged stair door should be corrected on the spot, and the reason it was wedged should be solved so it does not happen again.

Monthly inspection checklist

A trained member of the facility or maintenance team should inspect every fire door monthly and record the result.

CheckWhat good looks likeCommon fault
Self-closingDoor closes fully from any open positionCloser arm disconnected or closer leaking oil
LatchingLatch engages positively every timeStrike misaligned; latch taped back
Panic deviceBar retracts latch easily with one pushBar stiff, damaged or bypassed
HingesAll screws present and tight; no saggingMissing screws; leaf drags on floor
GapsEven gaps around leaf; no light visible at edgesUneven gaps from sagging or frame damage
SealsContinuous, undamaged, not painted overTorn, missing or painted seals
Vision glassIntact, firmly beadedCracked or replaced with ordinary glass
Leaf and frameNo holes, dents that affect closing, or rust throughHoles from removed fittings; impact damage
LabelsRating labels on leaf and frame visibleLabels painted over or removed
Magnetic holderReleases on test or alarmHolder not wired to alarm

Gaps deserve special attention. NFPA 80 sets maximum clearances for fire door assemblies; for steel doors, edge gaps of around 3 mm and bottom gaps of up to around 19 mm are the figures commonly cited. Confirm the limits that apply to your doors from the manufacturer's instructions and the edition of the standard your project follows.

Annual inspection and functional testing

NFPA 80, commonly specified for fire door installation and maintenance, calls for fire door assemblies to be inspected and tested at least annually by a person with knowledge of the doors and their hardware, with written records. Even where your project follows a different standard, an annual competent inspection is good practice.

An annual inspection should go further than the monthly check:

  1. Confirm each door matches its label and the door schedule: rating, size and type.
  2. Operate the door through its full range and check closing and latching speeds; adjust closers.
  3. Check hinge wear and fixings, frame anchorage and the seal between frame and wall.
  4. Inspect for unauthorised modifications: new holes, added locks, enlarged glass, cut-down leaves, added kick plates.
  5. Test hold-open release together with the fire alarm system.
  6. Check pairs close in sequence and the astragal overlaps correctly.
  7. Record every defect, the action required and the deadline.

For buildings with many doors, it helps to schedule the annual inspection alongside fire alarm and emergency exit lighting tests.

Common failures and how to fix them

FailureWhy it mattersCorrect fix
Door wedged or tied openDoor cannot close in a fireRemove wedge; install alarm-released magnetic holder if the door must stay open
Closer removed or disconnectedDoor will not close itselfRefit or replace with a listed closer sized for the leaf
Latch not engagingFire pressure can push the door openRealign strike; repair or replace with rated latch
Seals painted over or tornSmoke passes around the leafReplace with the manufacturer's specified seal
Gaps too largeSmoke and flame pathAdjust hinges; repair frame; consult manufacturer
Holes from removed fittingsBreaches the leafFill only by a method approved by the manufacturer
Ordinary glass in vision panelGlass fails early in a fireReplace with the correct fire-rated glass from the manufacturer
Padlock or bolt on escape doorPeople may be trappedRemove immediately; fit fire exit hardware
Non-rated lock or hinge fittedAssembly no longer as testedReplace with listed hardware

Most of these failures come from a real operational need: ventilation, trolley movement, security. Solve the need properly — with a hold-open device, a different door position or an access control solution approved for fire doors — or the fault will come back.

What you can and cannot repair on site

Routine maintenance such as tightening screws, adjusting closers, lubricating hinges and replacing seals with the specified type can usually be done by trained staff.

Do not do these on site without the manufacturer's approval:

  • Cutting or trimming the leaf or frame.
  • Enlarging or adding vision panels or louvres.
  • Drilling new holes for locks, signs or access control.
  • Replacing glass with anything other than the specified fire-rated glass.
  • Changing hinges, closers or exit devices for non-listed parts.

If a door is badly damaged, replacement is often cheaper and safer than repair. As the manufacturer of its doors, Safety Plus can supply matching replacement hardware or new doors to the original size; contact us through the request a quote page.

Record keeping: a simple fire door log

Give every fire door a unique ID (for example, "B-3F-ST2-01" for building B, third floor, stair 2, door 1), mark it on the floor plan, and keep a log like this:

FieldExample
Door ID and locationB-3F-ST2-01, stair 2 landing, 3rd floor
Rating and type120 min, single leaf, rock wool core
Manufacturer and label numberAs on leaf label
Inspection date and typeMonthly / annual
InspectorName and role
FindingsCloser slow to latch; seal torn at head
Action and deadlineAdjust closer; replace seal within 7 days
Date closed and by whomDate, name

Keep the log with the original door schedule, test evidence and hardware data sheets. These records also support your wider compliance file; see the BNBC 2020 fire safety overview for context. For replacement doors and hardware, see fire rated doors and fire door hardware.

Frequently asked questions

How often should fire doors be inspected?

A practical routine is quick walk-through checks daily or weekly, a recorded monthly inspection, and an annual inspection and test by a competent person, which NFPA 80 commonly requires.

Can a fire door be kept open during working hours?

Only with an alarm-released hold-open device, such as a magnetic door holder, that lets the closer shut the door when the alarm sounds or power fails. Wedges and hooks are never acceptable.

What gap is acceptable around a fire door?

Follow the manufacturer's instructions and the standard your project uses. For steel doors under NFPA 80, edge gaps of around 3 mm and bottom gaps of up to around 19 mm are commonly cited limits.

Who should carry out the annual fire door inspection?

A person with knowledge of fire door assemblies and their hardware, such as a trained facility engineer, the door manufacturer's technician or a fire safety consultant. The inspection should be documented.

Can we drill a fire door to fit an access control lock?

Not without the manufacturer's approval and suitable listed hardware. Unapproved holes can void the rating.